Outdoor Station Type 11kv-220kv Polymeric Lightning Arrester (type test)

Outdoor Station Type 11kv-220kv Polymeric Lightning Arrester (type test)

Repetitive charge transfer Qrs (C) is 0.5C,guaranted 2ms test current (A) is 400A,4/10µs high current test (kA)is 100kA. suggested rated voltage (kV)is 3.2kV or 5.5kV

Product Details

We are going to continue to lead the pursuit of excellence created a unique and exquisite Metal Oxide Varistors For Station Arresters, metal oxide varistor leakage current, glass coating Metal Oxide Varistors, working together to build a new world with the community. We have established a perfect modern management mechanism on the basis of having a group of high quality technicians and professional talents. We have been perfectly devoted to the design, R&D, manufacture, sale and service of hair products during 10 years of development. In order to improve our product innovation ability, we put forward the product development concept of knowledge driven collaborative innovation.


MOV Blocks diameter from 38mm to 40mm.


AC systemACACACACACAC
typeD38H20.7D38H31D38H34.5D40H20.7D40H31D40H34.5
suggested rated voltage (kV)3.24.95.43.34.95.5
MCOV (kV)2.84.14.62.84.24.6
diameter (mm)38.5±0.738.5±0.738.5±0.740±0.740±0.740±0.7
height (mm)23.5±0.329±0.335±0.323.5±0.329±0.335±0.3
DC U1mA (kV)4.85±0.37.3±0.458.1±0.54.85±0.37.3±0.458.1±0.5
IL at 75% of U1mA(µA)≤ 15≤ 15≤ 15≤ 15≤ 15≤ 15
Ures(kV)8.6±0.512.9±0.814.35±0.88.5±0.512.8±0.814.2±0.8
typical Ures / U1mA1.771.771.771.751.751.75
repetitive charge transfer Qrs (C)0.50.50.50.50.50.5
guaranted 2ms test current (A)400400400400400400
max 2ms test current (A)450450450500500500
4/10µs high current test (kA)100100100100100100
nominal discharge current In (kA)101010101010
accelerated ageing test115℃ 0.9*U1mA/√2
Kct ≤ 1.0
115℃0.9*U1mA/√2
Kct ≤ 1.0
115℃ 0.9*U1mA/√2
Kct ≤ 1.0
115℃ 0.9*U1mA/√2
Kct ≤ 1.0
115℃0.9*U1mA/√ Kct ≤ 1.0115℃0.9*U1mA/√2
Kct ≤ 1.0


MOV Blocks diameter from 38mm to 40mm.

AC systemACACACACACAC
typeD38H20.7D38H31D38H34.5D40H20.7D40H31D40H34.5
suggested rated voltage (kV)3.24.95.43.34.95.5
MCOV (kV)2.84.14.62.84.24.6
diameter (mm)38.5±0.738.5±0.738.5±0.740±0.740±0.740±0.7
height (mm)23.5±0.329±0.335±0.323.5±0.329±0.335±0.3
DC U1mA (kV)4.85±0.37.3±0.458.1±0.54.85±0.37.3±0.458.1±0.5
IL at   75% of            U1mA(µA)≤ 15≤ 15≤ 15≤ 15≤ 15≤ 15
Ures(kV)8.6±0.512.9±0.814.35±0.88.5±0.512.8±0.814.2±0.8
typical Ures / U1mA1.771.771.771.751.751.75
repetitive charge transfer Qrs (C) 0.50.50.50.50.50.5
guaranted 2ms test current (A)400400400400400400
max 2ms test current (A)450450450500500500
4/10µs high current test (kA)100100100100100100
nominal discharge current In (kA)101010101010
accelerated ageing test115℃ 0.9*U1mA/√2
 Kct ≤ 1.0
115℃0.9*U1mA/√2
 Kct ≤ 1.0
115℃ 0.9*U1mA/√2
 Kct ≤ 1.0
115℃ 0.9*U1mA/√2
 Kct ≤ 1.0
115℃0.9*U1mA/√ Kct ≤ 1.0115℃0.9*U1mA/√2
 Kct ≤ 1.0


We are always ready to provide customers with thoughtful Outdoor Station Type 11kv-220kv Polymeric Lightning Arrester (type test) solutions, products and services, and we can meet customer needs in a very short time. It's our responsibility to guarantee the quality of products. It is well received by users in various industries.
Hot Tags: mov blocks diameter from 28mm to 42mm China, suppliers, manufacturer, factory, distribution class, high voltage, high performance, medium voltage, test, size, best, IEC 60099-4 2014, distribution networks, components of metal oxide arrester size, metal oxide varistors for arrester, best High Voltage Station Arrester, varistor surge protection, metal oxide varistor description, MOV For High Gradient AC Arresters