Lightning Surge Protector/AC Power Surge Protection Device

Lightning Surge Protector/AC Power Surge Protection Device

10kV Arresters diameters 28mm 30mm zinc oxide varistors,repetitive charge transfer Qrs (C) is 0.3C,guaranted 2ms test current (A) is 150A,4/10µs high current test (kA)is 65kA. suggested rated voltage (kV)is 3.6kV or 4.5kV

Product Details

We promise to offer all customers with safe, assured and high-quality metal oxide varistor testing pdf, Nominal Discharge Current 2.5kA MOVs, polymer-housed surge arresters test and services with solid professional knowledge and scientific and effective service concepts. In the increasingly fierce competition, technology changes with each passing day, our company pays attention to science and technology, attaches importance to information. We constantly improve and perfect our products and services so that to create a first-class brand with long-term vitality. We change the sales model of traditional product distributors, synchronize online and offline operations, do promotion and operation online and sales and service offline. Our goal is great, so our company has made great progress.

10kV Arresters which use diameters 28mm or 30mm zinc oxide varistors.

type D28H23.5 D28H29 D30H23.5 D30H29
AC system AC AC AC AC
suggested rated voltage (kV) 3.6 4.5 3.6 4.5
MCOV (kV) 3.1 3.8 3.1 3.8
diameter (mm) 28±0.7 28±0.7 30±0.7 30±0.7
height (mm) 23.5±0.3 29±0.3 23.5±0.3 29±0.3
DC U1mA (kV) 5.52±0.3 6.82±0.35 5.52±0.3 6.82±0.35
IL at 75% of U1mA
(µA)
≤ 10≤ 10≤ 10≤ 10
Ures (kV) 9.7±0.5 12.0±0.6 9.5±0.5 11.7±0.6
typical Ures / U1mA 1.75 1.75 1.72 1.72
repetitive charge transfer Qrs (C) 0.3 0.3 0.3 0.3
guaranted 2ms test current (A) 150 150 150 150
max 2ms test current (A) 150 150 200 200
4/10µs high current test (kA) 65 65 65 65
nominal discharge current In (kA) 5 5 5 5
accelerated ageing test 115℃
0.9*U1mA/√2
Kct ≤ 1.0
115℃
0.9*U1mA/√2
Kct ≤ 1.0
115℃
0.9*U1mA/√2
Kct ≤ 1.0
115℃
0.9*U1mA/√2
Kct ≤ 1.0


type D28H23.5 D28H29 D30H23.5 D30H29
AC system AC AC AC AC
suggested rated voltage (kV) 3.6 4.5 3.6 4.5
MCOV (kV) 3.1 3.8 3.1 3.8
diameter (mm) 28±0.7 28±0.7 30±0.7 30±0.7
height (mm) 23.5±0.3 29±0.3 23.5±0.3 29±0.3
DC U1mA (kV) 5.52±0.3 6.82±0.35 5.52±0.3 6.82±0.35
IL at   75% of U1mA
    (µA)
≤ 10≤ 10≤ 10≤ 10
Ures   (kV) 9.7±0.5 12.0±0.6 9.5±0.5 11.7±0.6
typical Ures / U1mA 1.75 1.75 1.72 1.72
repetitive charge transfer Qrs (C)  0.3 0.3 0.3 0.3
guaranted 2ms test current (A) 150 150 150 150
max 2ms test current (A) 150 150 200 200
4/10µs high current test (kA) 65 65 65 65
nominal discharge current In (kA) 5 5 5 5
accelerated ageing test 115℃
 0.9*U1mA/√2
    Kct ≤ 1.0

115℃ 

0.9*U1mA/√2

    Kct ≤ 1.0
115℃
0.9*U1mA/√2
    Kct ≤ 1.0
115℃
 0.9*U1mA/√2
    Kct ≤ 1.0


We strive to ensure customer experience after product delivery and enhance the added value of our Lightning Surge Protector/AC Power Surge Protection Device. The perfect integration of business model and innovative technology makes our company better create value for customers and strengthen our long-term cooperation with customers. Our company has strong economic and technical strength and strict management. After continuous construction and development, we have gradually formed a diversified development pattern of domestic and foreign trade. Our products are sold well in various regions at home and abroad.
Hot Tags: 10kv arresters diameters 28mm 30mm zinc oxide varistors China, suppliers, manufacturer, factory, distribution class, high voltage, high performance, medium voltage, test, size, best, IEC 60099-4 2014, distribution networks, Low Voltage Distribution Arrester, porcelain surge arrester size, Nominal Discharge Current 2.5kA MOVs, D62 Movs For Arresters size, metal oxide varistor pdf specificationm, varistor surge protection